industrial and commercial buildings. These transmitters can be used for indoor air temperature and humidity monitoring in various industrial plant, clean room, lab, machine room, office and airport, station, library and stadium, etc.
* Multiple output signals selectable
Type:
GE-373-TH-01 Temp./RH transmitter without LCD
GE-373-TH-02 Temp./RH transmitter with LCD Screen
Specifications:
Relative Humidity:
* Sensor: Capacitance polymer
* Range: 0~100%RH
* Output: 4~20mA / 0~10VDC / RS485
* Accuracy: 2%, 3% and 4.5%RH(25°C, 20~80%RH)
* Hysteresis: ﹤±1%RH
* Response time: ﹤10s ( 25 C, in slowly flow air)
* Drift: ﹤±0.5%RH/year
Temperature:
Sensor: Solid state band gap, RTD or thermistors
Range: 0~50°C for transmitter or other
Output: 4~20mA/0~10V/RS485, RTD or thermistors
Accuracy: ﹤±0.5 C @ 25 C
Electronic:
Power: Voltage 15~35VAC/DC, current 7.5-36VDC
Output Load: <500Ω (current), >2KΩ (voltage)
Display: Large LCD screen digital display, optional
Display Accuracy: 0.1°C, 0.1%RH
Display Resolution: 0.1°C, 0.1%RH
Temperature Limit: 0~70°C, 0~95%RH (Non condensing)
Storage Temperature: -20~80°C
Housing: ABS Enclosure
Protection: IP30
Option:
RH Accuracy:±2%RH, ±3%RH; ±4.5%RH
RH Output: 0-10VDC; 4-20mA; RS485, Modbus
Temperature Range: 0-50C; 0-100C; -40-60C;
Temperature Output: 10-10VDC 4-20mA; 2 PT1000, ±0.2℃@25℃; 3 PT100, ±0.2℃@25℃;
4NTC20K, ±0.2℃@25℃; 5Ni 1000, ±0.4℃@25℃; 6NTC10K,±0.2℃@25℃
7 RS485,Modbus
Contact: Mr.Robert
Phone: 0086-13166369204
Tel: 400-852-8332
Email: hongkong@ayite.net
Add: Building 17 &22, No.2928, Chuan Zhou Highway, Shanghai, 201319, China